Unsprinklered space intended for temporary use

With the growing popularity of (video) calls, single-person call booths are increasingly being installed in buildings. These call booths provide a soundproof environment where you can make calls or hold video conferences without interruption. They have a maximum area of 2 m² and are equipped with ventilation, but are not designed for prolonged use. The question is whether these single-person call booths must be equipped separately with surveillance and evacuation alarm systems in a building that already has a fire alarm or evacuation alarm system.

Continue reading
Employees meeting in a conference room with glass walls during a business meeting.

An initial response to this came on June 4 in the form of the CCV’s interpretive decision titled “Monitoring and Detection of Single-Person Call Booths.” However, there was still uncertainty regarding fire suppression (sprinkler or water mist). This matter has now been clarified, and on November 28, a harmonization agreement was published regarding non-sprinklered spaces intended for temporary use.

Permissible Limit

A non-sprinklered space intended for temporary use—such as a phone booth, a meeting room, or a quiet area—may be excluded from sprinkler protection under the following conditions:

  • The space is intended for short-term, temporary use;
  • There is at least 500 mm of clearance between the ceiling above and the sprinklers located below it, or—if there is less than 500 mm of clearance—the sprinklers are properly designed in relation to the space(s);
  • The space is separate from the sprinkler-protected area, and if more than one non-sprinklered space intended for temporary use is present, there is at least 150 mm of separation between them so that they do not form a continuous whole;
  • The area of the space does not exceed 2.2 m² and is not used for storage;

These new guidelines significantly improve safety in buildings with phone booths. They ensure that these small spaces are not only practical but also comply with the fire safety standards that are essential for the well-being of building occupants. The full Harmonization Document can be found here.

Do you have phone booths in your building?

Check to see if they meet the latest safety requirements. Fire safety begins with compliance with the appropriate standards and guidelines.

Looking for an independent inspection partner?

Normec offers expert and independent inspections for safe buildings, installations, and facilities.

Contact us

Complete the form and we will contact you as soon as possible.
Naam
Privacy Policy 

Request a quote

Fill out the form and we will contact you shortly.

Naam
Privacy Policy 

Related articles

15 Jul 2025

New CCV Agreement: Sprinkler Heads May Be Retained Under Certain Conditions

The Center for Crime Prevention and Safety (CCV) has published the new harmonization agreement 2025-01. This agreement concerns the replacement of sprinkler heads during their service life. The agreement provides clarity on situations in which sprinkler heads may remain in place even after their specified service life has expired.

Emergency responders are fighting a fire with foam and water during an incident at an outdoor site.
15 Jul 2025

Extensive damage

In the German town of Stadtallendorf, a fire station was completely destroyed by a fire. The fire was able to spread unchecked because part of the station—which had only opened in January—did not have a sprinkler system or fire alarm. The damage is estimated at at least 20 million euros.

Close-up of a sprinkler head attached to a red pipe that disperses a fine mist of water. The image illustrates an automatic fire suppression system for fire safety in buildings and industrial environments.
15 Jul 2025

Preventing a Devastating Disaster

On Saturday, December 28, at the Vossenberg industrial park in Tilburg, it became clear once again just how essential sprinkler systems are for the safety of people and buildings. A fire broke out in a Tesla battery storage warehouse, but thanks to a properly functioning and certified sprinkler system, it did not escalate into a devastating disaster.

A technical staff member conducts an inspection using a tablet in an industrial production environment.
09 Sep 2026

Technical Bulletin 64-2024 on Foam Additive Dosing Systems

On October 2, 2024, the revised Technical Bulletin TB 64-2024 was published. This bulletin, titled “Foam Concentrate (SVM) Proportioning Systems,” replaces the previous TB 64B. This comprehensive revision marks an important step in clarifying and updating the application of standards regarding FMA dosing systems in all types of fixed fire sprinkler systems (VBB systems).

An inspection of a steel structure in an industrial setting.
15 Jul 2025

New standard published

Euralarm has published a new guideline on the impact of high airflow rates and hot/cold aisle containment on the operation of gaseous fire suppression systems in data centers. The guideline is intended for fire protection system designers, IT managers, and data center operators.

Related services

An individual operates a touchscreen on laboratory equipment to set up or monitor an analysis process.

Fire Alarm Testing and Inspections

Red industrial pipes with sprinkler heads in a fire protection system

Fire suppression inspections