Accessibility links Skip to main content

Easily Test Overcurrent Protection Devices Using Loop Impedance

On the GP Prüfservice GmbH blog, our experts regularly address questions about electric motors and electrical systems and explain technical terms. Here, we’ll focus on how to easily test overcurrent protection devices using loop impedance. We also answer the frequently asked question of whether loop impedance can be measured with a multimeter.

Continue reading

On the GP Prüfservice GmbH blog, our experts regularly address questions about electric motors and electrical systems and explain technical terms. Here, we focus on how to easily test overcurrent protection devices using loop impedance. And we answer the frequently asked question of whether loop impedance can be measured with a multimeter.

Contents of this article

  • What Is the Purpose of Measuring Loop Impedance
  • Relevant standards for determining loop impedance
  • Measuring and Testing Equipment: Can I Measure Loop Impedance with a Multimeter?
  • The influence of the power supply configuration according to DIN VDE 0100 on loop impedance
  • How do you calculate loop impedance?

Questions about electrical testing? Get advice now!

When calculating alternating currents, impedance is the counterpart to ohmic resistance in direct current systems. You’ll encounter the term “loop impedance” particularly when designing and testing overcurrent protection devices. Here, it refers to the total AC resistance of the current loop that, in the event of an insulation fault, flows from an outer conductor through the protective conductor and the connected structure back to the outer conductor.

Have it inspected by an expert

GP Prüfservice GmbH has more than 50 years of experience with electric motors and the testing of electrical systems and equipment. Get a no-obligation consultation today.

What is the purpose of measuring loop impedance?

The practical significance of loop impedance (ZS) in connection with overcurrent protection devices lies in the fact that a certain minimum current is required to ensure sufficiently rapid activation of the circuit breaker. The short-circuit current itself is generally very difficult to determine. Measuring the loop impedance, on which it depends, is, however, simple. For example, for a circuit breaker with Class B characteristics in accordance with DIN VDE 0641 in a 230 V AC circuit with a rated current of 16 A, the loop impedance must not exceed 2.88 Ω.

Relevant Standards for Determining Loop Impedance

To determine the loop impedance, one must first consider the DIN VDE 100 series of standards, which deals with the installation of low-voltage systems up to 1,000 V AC or 1,500 V DC. Of particular interest is Group 400, “Protective Measures,” and within it, the standard DIN VDE 0100-430, “Protection of Cables and Wires Against Overcurrent.”

Further important information and definitions can be found in the DIN VDE 0413 standard, which addresses the design requirements for test equipment, such as that used for loop impedance measurement, for example, in DIN VDE 0413 Part 4, which specifies requirements for measuring instruments, and in Part 3, which addresses permissible user errors.

Guidelines for the design of standard household circuit breakers can be found in the DIN VDE 0641 standard. The DIN VDE 0660 standard, in turn, addresses switching devices and their combinations in its various parts.

The influence of the power supply configuration according to DIN VDE 0100 on loop impedance

The relevant regulations and standards permit several circuit configurations with regard to grounding. These are identified by letter combinations. The first character describes the grounding of the power source. Here, a “T” indicates a direct ground connection at a single point, while an “I” indicates that all live parts are isolated from ground potential or that only a connection via an impedance exists.

A second digit indicates the grounding of the electrical system’s structure. Here, too, a “T” indicates direct grounding at a single point, regardless of the power source’s grounding. In TN systems, however, grounding is provided via a service grounding conductor, which is in turn directly connected to earth.

An optional additional letter, which may be appended with a hyphen, is relevant for determining the loop impedance. It provides information about the use of neutral (N) and protective conductors (PE). In a TN-C system, these are combined into a PEN conductor. While you normally measure the loop impedance between the line (L) and protective conductor, separate from the neutral conductor, the second measurement point for loop impedance in such a system configuration is the PEN conductor.

Measuring and Testing Equipment: Can I measure loop impedance with a multimeter?

A frequently asked question regarding loop impedance is:

Question: Can I measure loop impedance with a multimeter?

Answer: No. Specialized test equipment is required to measure loop impedance.

To explain why, we need to go into a bit more detail: While determining the measured quantities required to calculate loop impedance and other parameters of low-voltage equipment is, in principle, within the capabilities of commercially available multifunction testers—so-called multimeters— However, handheld multimeters—which are particularly well-suited for mobile use—often lack the necessary performance capabilities.

For example, digital multimeters cannot provide the current required for a correct determination of loop impedance during resistance measurement. They therefore do not meet the requirements specified in DIN VDE 0413 Part 4 and are thus unsuitable.

Requirements for Measurement and Test Equipment

The measurement voltage must be between 4 and 24 V. The measurement currents must be at least 0.2 A for direct current or at least 5 A for alternating current.

For loop impedance measurement and other installation tests, special test equipment is therefore generally required; this equipment is marketed as loop resistance testers. Such installation testers usually offer the additional advantage of supporting the creation of the required test reports, for example, through appropriate data storage capabilities. Since loop resistance testers are quite expensive compared to a multimeter, outsourcing the necessary tests is usually the better solution, especially for smaller companies. GP Prüfservice GmbH would be happy to provide you with a quote.

‍

How is loop impedance calculated?

Now that we’ve covered the meaning, regulations, and requirements for measuring instruments, the question remains: how is loop impedance actually calculated? You can determine the loop impedance ZS from the measurement voltage and the measurement current between a phase conductor and the protective conductor, or the PEN conductor in a TN-C system. The calculation is performed using the equation ZS = U0 / Ia, where U0 denotes the rated voltage (since 1987, 230 V single-phase / 400 V three-phase) and Ia denotes the trip current.

For circuit breakers with characteristic B according to DIN VDE 0641, Ia should be set to five times the rated current IN of the protective device; for circuit breakers with characteristic C, it should be set to ten times the rated current. This results, for example, in maximum permissible values for the loop impedance of circuit breakers with characteristic B in a 230 V system of:

  • 7.3 Ω at IN = 6 A
  • 4.6 Ω at IN = 10 A
  • 2.88 Ω at IN = 16 A
  • 2.3 Ω at IN = 20 A
  • 1.84 Ω at IN = 25 A
  • 1.44 Ω at IN = 32 A

According to the version updated in 2007, when determining the loop impedance, the increase resulting from the heating of the conductors in the event of a fault must also be taken into account. For this reason, the initially determined value of the loop impedance must be corrected by a factor of 2/3. The example table then looks as follows:

  • 4.87 Ω at IN = 6 A
  • 3.07 Ω at IN = 10 A
  • 1.92 Ω at IN = 16 A
  • 1.53 Ω at IN = 20 A
  • 1.23 Ω at IN = 25 A
  • 0.96 Ω at IN = 32 A

In addition, further corrections for measurement errors in the test equipment must be taken into account, which, according to DIN VDE 0413 Part 3, are set at 30%. The actual current may therefore deviate from the measured value by between -23% and +43%.

What should be considered when testing loop impedance?

In addition to the impedances of the outer conductor and the protective conductor (or PEN conductor), the loop impedance also includes the AC resistance of the current source. The accuracy of the loop impedance measurement depends on the stability of the voltage during the measurement process. For trip times, which—in accordance with the standard—may be 0.2, 0.4, or 5 seconds depending on the characteristics of the respective circuit, it is recommended to verify the measurement results by taking multiple measurements.

If the required loop impedance values are not achieved during the inspection of the electrical installation, you can ensure the effectiveness of the protective device by taking the following measures, among others.

  1. Installing a new conductor with a larger cross-section.
  2. Installing an additional residual-current circuit breaker (RCCB). The overcurrent protection device then serves only to protect the circuit. Dangerous body currents, on the other hand, are interrupted early by the RCCB.

We’d be happy to advise you!

GP Prüfservice GmbH in Dortmund is your expert for DGUV V3 inspections. Our team has more than 50 years of experience with electric motors and industrial services. We handle the inspection of electrical systems and equipment for you in North Rhine-Westphalia and nationwide.

Are you looking for an independent inspection partner?

Normec offers expert and independent inspections for safe buildings, systems, and facilities.

Contact us

Complete the form and we will contact you as soon as possible.
Naam
Privacy Policy 

Request a quote

Fill out the form and we will contact you shortly.

Naam
Privacy Policy 

Related Articles

A technician performs inspection or maintenance work on an open electrical control panel.
19 Aug 2026

Inspection of Stationary Electrical Systems

Fixed electrical installations must be inspected by a qualified electrician after commissioning, after modifications, and at regular intervals. With more than 50 years of experience in industrial services, GP Prüfservice knows exactly what matters.

A technician is taking measurements inside an open electrical control panel containing wiring and components.
19 Aug 2026

DGUV V3 Inspection Costs: How Much Does an E-Check Cost?

The regular DGUV V3 inspection, also known as an E-Check, is required by law. In this blog post, learn how the costs for a DGUV V3 inspection are broken down—and how you can get a specific quote by scheduling a free trial inspection with the experts at GP Prüfservice.

A person records inspection data on a clipboard during an inspection in an industrial setting.
19 Aug 2026

E-Check: Why Inspecting Equipment Is So Important

The E-Check—the professional inspection of electrical equipment and systems—is mandatory for companies in Germany. We explain why this is the case and when you’re on the safe side.

19 Aug 2026

How to Test a Three-Phase Motor Using Simple Methods

Three-phase motors are the workhorses of the electric motor world and can start even when faced with high countertorques. In this article, we’ll explore how to test a three-phase motor using simple methods.

An electrical technician performs an insulation resistance test in a meter box while wearing protective insulation gloves.
19 Aug 2026

Electric Motor Troubleshooting: Check the Motor Capacitor

Most electric motors that run on standard 230-volt AC power from a wall outlet are so-called capacitor motors. When such a capacitor motor fails, the component that gives it its name is often to blame.

Fixed industrial ladder and platform structure on a factory premises providing access to elevated facilities.
19 Aug 2026

DC Motor Maintenance—Explained Step by Step

Regular maintenance and servicing of electric motors can minimize downtime, reduce the failure rate during electrical testing, and thus make a significant contribution to the success of an industrial operation. In this article, we explain how regular maintenance of DC motors is carried out.

19 Aug 2026

The Electric Motor Won’t Start – Diagnostic Tips from an Expert

From commercial kitchen range hoods to high-pressure washers, from circular saws to forklifts—in many areas, we depend on electric motors to function. The experts at GP Prüfservice offer tips for when an electric motor stops working.

Related Services

Expert die een brandveiligheidsinspectie uitvoert met behulp van een VDS-inspectie voor het controleren van de brandveiligheid in een gebouw.

VdS expert examination

Low-Voltage Inspection

Renewable Energy Systems

DGUV V3 Testing

Thermography

Equipment Testing

Machine Safety